ATEX LIGHTING

ATEX Hazardous Area Lighting – Zones, Ex Markings & LED Lighting Guide

A guide to specifying ATEX LED lighting for hazardous areas: zone classification, how to read Ex markings, ATEX versus IECEx, system architecture and how to specify a compliant LMX ATEX LED strip system for Zones 1, 2, 21 and 22.

01

What is ATEX lighting?

ATEX lighting is equipment certified for use where flammable gases, vapours, mists or combustible dusts may be present. ATEX is the European framework made up of Directive 2014/34/EU (equipment) and Directive 1999/92/EC (workplaces). Equipment is assessed against the EN IEC 60079 series of standards.

The hazardous-area classification sets the equipment protection and certification required. It does not set the illuminance (lux) required for the task — that is determined separately (see Section 10).

02

Hazardous-area zones

Hazardous areas are classified into zones based on the likelihood of an explosive atmosphere being present. Gas zones (0/1/2) and dust zones (20/21/22) are classified and marked separately. A product certified for gas is not automatically certified for dust, and the reverse is also true.

Zones are established by the site's area classification study (EN/IEC 60079-10-1 for gas, 60079-10-2 for dust).

ZONE
HAZARD
DESCRIPTION
0
Gas / vapour
Present continuously, for long periods or frequently
1
Gas / vapour
Likely to occur occasionally in normal operation
2
Gas / vapour
Not likely in normal operation; if it occurs, only briefly
20
Dust
Present continuously, for long periods or frequently
21
Dust
Likely to occur occasionally in normal operation
22
Dust
Not likely in normal operation; if it occurs, only briefly

SOURCE: EN/IEC 60079-10-1 (GAS) · EN/IEC 60079-10-2 (DUST)

The LMX ATEX LED strip (Category 2, EPL Gb/Db) is suitable for Zones 1, 2, 21 and 22, subject to correct selection and installation. It is not suitable for Zone 0 or Zone 20.

03

LMX ATEX LED Strip

  • Zones 1 / 2 and 21 / 22, subject to correct selection and installation
  • II 2G Ex mb op is IIC T4 Gb
  • II 2D Ex mb op is IIIC T135°C Db
  • IP67 · IK10
  • Operating temperature −40°C to +80°C
  • 24 / 36 / 48V AC or DC depending on configuration
  • White AC: 800 lm/m, 12 W/m
  • White DC: up to 1,000 lm/m, 12 W/m
  • Additional 24V DC version: 500 lm/m, 6 W/m
  • White CCT: project selectable
  • Colours: White / Amber / Green / Red

LED Strip: ATEX documentation confirmed.

Explosion-Proof Enclosure: ATEX and IECEx documentation available.

ENCLOSURE CERTIFICATES: ATEX TPS 20ATEX 106819 0002 X REV.00 · IECEX IECEX NEP 20.0007X

The LED strip is not described as IECEx certified. The strip and the enclosure are separately certified — see Section 6.

04

How to read the Ex marking

The Ex marking on the LMX ATEX LED Strip is read element by element. The full gas and dust markings are shown below with a concise explanation of each element.

GAS MARKING

II 2G Ex mb op is IIC T4 Gb

MARKING
MEANING
II
Equipment Group II (surface industries)
2G
Category 2 gas equipment
Ex
Explosion-protected equipment
mb
Encapsulation protection
op is
Inherently safe optical radiation
IIC
Gas group IIC (most demanding gas group)
T4
Maximum surface temperature associated with T4 is 135°C
Gb
Equipment Protection Level Gb (Zones 1 and 2)
DUST MARKING

II 2D Ex mb op is IIIC T135°C Db

MARKING
MEANING
II
Equipment Group II (surface industries)
2D
Category 2 dust equipment
Ex
Explosion-protected equipment
mb
Encapsulation protection
op is
Inherently safe optical radiation
IIIC
Conductive dust group (most demanding dust group)
T135°C
Dust maximum surface-temperature marking
Db
Equipment Protection Level Db (Zones 21 and 22)
05

ATEX versus IECEx

ATEX is the European framework for explosive-atmosphere equipment. IECEx is an international certification system based on the IEC 60079 standards. They are separate certifications: holding one does not mean you hold the other.

LED Strip — ATEX documentation confirmed.

Explosion-Proof Enclosure — ATEX & IECEx documentation available.

06

System architecture

POWER PATH

Mains Supply → Explosion-Proof Power / Driver Enclosure → Low-Voltage ATEX LED Strip

The ATEX LED strip is never connected directly to mains. Mains power is fed into an explosion-proof power/driver enclosure, which supplies low-voltage DC to the strip.

Available enclosure/system information:

  • 100–240V / 277V AC input options
  • 12 / 24 / 36 / 48V DC outputs
  • up to 200W
  • Mean Well driver documented in current system

The final driver and enclosure depend on each project's configuration.

07

Emergency lighting option

An optional configured emergency system is available at approximately 12W / 1.5 hours.

This is a system/power configuration, not an inherent battery duration of the LED strip itself. The required emergency duration depends on the applicable standards (BS EN 1838 / BS 5266-1), the evacuation strategy and the project risk assessment, and must be checked for each installation.

08

ATEX is not a lux level

ATEX and the hazardous-area classification determine the equipment protection and certification required in an area. They do not determine the illuminance required for the task. Required illuminance is determined separately — by the task, the workplace lighting standards (BS EN 12464 series), the emergency lighting standards (BS EN 1838 / BS 5266-1) and the project specification.

09

Information required for an ATEX lighting design

Have the following information ready when requesting an ATEX lighting design:

  • Gas or dust environment
  • Zone classification
  • Gas group and/or dust group
  • Temperature requirements (temperature class / maximum surface temperature)
  • Ambient temperature range
  • Required lux levels for the task
  • Run length
  • Supply voltage
  • Mounting arrangement
  • Emergency lighting requirement and duration
  • Certification requirements (ATEX and/or IECEx as required by the project or country)
10

LMX ATEX Lighting Design

LMX can select and design the ATEX LED strip system around the hazardous-area classification and the required lighting performance for the project. Because every hazardous-area installation is different, LMX does not publish generic photometric figures as if they were universal results.

A project-specific design addresses the zone, gas/dust group, temperature class, run length, supply arrangement, mounting, emergency requirement and the certification scheme the project requires.

Need an ATEX lighting design? Our engineering team can configure the system around your hazardous-area classification and required lighting performance.

REQUEST AN ATEX LIGHTING DESIGN
11

Relevant LMX products

Lighting requirements vary according to the hazardous-area classification, gas/dust group, temperature class, task, risk assessment and project specification. The applicable standards, certification and project requirements should be confirmed for each installation.

base44
Edit with Base44